| Battery Input Data |
| Battery Type |
Lead-acid or Lithium-ion |
| Battery Voltage Range (V) |
40-60 |
| Max. Charging Current (A) |
220 |
250 |
290 |
| Max. Discharging Current (A) |
220 |
250 |
290 |
| Charging Strategy for Li-ion Battery |
Self-adaption to BMS |
| Number of Battery Input |
2 |
| PV String Input Data |
| Max. PV Access Power (W) |
24000 |
28000 |
32000 |
| Max. PV Input Power (W) |
19200 |
22400 |
25600 |
| Max. PV Input Voltage (V) |
500 |
| Start-up Voltage (V) |
125 |
| MPPT Voltage Range (V) |
150-425 |
| Rated PV Input Voltage (V) |
370 |
| Max. Operating PV Input Current (A) |
26+26+26 |
26+26+26 |
26+26+26 |
| Max. Input Short-Circuit Current (A) |
44+44+44 |
44+44+44 |
44+44+44 |
| AC Input/Output Data |
| Rated AC Input/Output Active Power (W) |
12000 |
14000 |
16000 |
| Max. AC Input/Output Apparent Power (VA) |
13200 |
15400 |
17600 |
| Rated AC Input/Output Current (A) |
54.5/52.2 |
63.6/60.9 |
72.7/69.6 |
| Max. AC Input/Output Current (A) |
60/57.4 |
70/67 |
80/76.5 |
| Max. Continuous AC Passthrough (grid to load) (A) |
100 |
100 |
100 |
| Peak Power (grid to load) (W) |
2 times of rated power, 10s |
| Power Factor Adjustment Range |
0.8 leading to 0.8 lagging |
| Rated Input/Output Voltage Range (V) |
220/230, 0.85Un-1.1Un |
| Rated Input/Output Grid Frequency/Range(Hz) |
50/45-55, 60/55-65 |
| Grid Connection Form |
L-N-PE |
| Total Current Harmonic Distortion THDi |
<3% (of nominal power) |
| DC Injection Current |
<0.5% In |
| Equipment Protection |
| Integrated |
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Detection and Protection, Output Residual Current Detection, Switch Insulation Impedance Detection, DC Disconnect, Circuit Breaker |
| Surge Protection Level |
TYPE II(DC), TYPE II(AC) |